Kyoritsu 6310 Power Quality Analyzer 
Keterangan
 
 • Can measure Flicker in accordance to IEC 61000-4-15 and EN50160 
standards. Using our Flicker sensor, available as optional accessory, 
Pst value ( short term severity in 10 minutes value) and the Plt value (
 long term severity in 2 hours value) can be measured.
 • 12 kinds of Power Measurements for Power Control and Applicable to Power Quality Control including Harmonics Analysis.
 • One click easy-to-use operation helps complicated setting and 
processing of large data through the setting / analyzing software 
provided as accessory.
 • Direct communication with PC via USB cable
 • Built-in Input / Output Function of external signal enables the signal transmission to alarms.
 • 2-way power supply by AC and Battery, and Nickel hydrogen battery usable with rechargeable function.
 • Pull / Insert of CF card possible whenever on recording under the function of memory backup device ( 1GB usable) .
 • Can monitor insulation at leakage current by using optional leak clamp sensors.
 • Built-in Print Screen Function enables to record display screen ( Records 512 screens by using CF card: 1 screen 40KB) .
 • Can display Waveform and Vector, and can confirm the wiring connection, too.
 • Complies fully with International Safety Standards
 IEC 61010-1 CAT.III 600V.
 
 * Attention for KEW6310 customers: 
 
 Flicker measurements are possible with firmware of KEW6310 upgrade ( 
Ver.2.01) , PC software PQA Master upgrade ( Ver. 2.01) and an optional 
accessory Flicker sensor KEW8325F.
 
 Wiring connections : 1P 2W, 1P 3W, 3P 3W, 3P 4W
 Measurements and parameters : Voltage, Current, Frequency, Active power, Reactive power, 
 Apparent power, Active energy, Reactive energy, Apparent energy, 
 Power factor ( cos ¸ ) , Neutral current, Demand, Harmonics, 
 Quality ( Swell/ Dip/ Instantaneous Stop, Transients/ Over Voltage, 
Inrush Current, Unbalance Rate, IEC Flicker [ Pst( 1 min) * , Pst, Plt] )
 , Phase Advance Condenser
 
 ( * Pst can be shown in details for 1 minute intervals.) 
 Other functions : Digital output function, External communication function, 
 Scaling function
 Voltage : 
 Ranges [ RMS] : 150 / 300 / 600 / 1000V ( CF: 2.5 or less, 100% or less of each range) 
 Allowable input : 10~ 110% of each range ( 1000V range : 20% ~ ) 
 Display ranges : 5~ 120% of each range
 Accuracy : ± 0.3% rdg± 0.2% f.s. ( sine wave, 45~ 65Hz) 
 Current : 
 Ranges [ RMS] : 8128 ( 50A type ) : 1 / 5 / 10 / 20 / 50A
 8127 ( 100A type ) : 10 / 20 / 50 / 100A
 8126 ( 200A type ) : 20 / 50 / 100 / 200A
 8125 ( 500A type ) : 50 / 100 / 200 / 500A
 8124 ( 1000A type ) : 100 / 200 / 500 / 1000A
 8129 ( 3000A type ) : 300 / 1000 / 3000A
 ( CF: 3.0 or less. 90% or less of each range) 
 Allowable input : 10~ 110% of each range
 Display ranges : 1~ 120% of each range
 Accuracy : ± 0.3% rdg± 0.2% f.s. + Accuracy of Clamp sensor
 ( sine wave, 45~ 65Hz) 
 Activa power accuracy : ± 0.3% rdg± 0.2% f.s. + Accuracy of Clamp sensor
 ( Power factor 1, Sine wave, 45~ 65Hz) 
 Influence of power factor : ± 1.0% rdg ( reading at power factor 0.5 against power factor 1) 
 Frequency meter range : 40~ 70Hz
 Internal memory : 1.8MB
 Measurement file ( CSV) : 256kB× 6 blocks ( = 1.536MB) 
 Screen file ( BMP) : 32kB× 7 blocks ( = 0.224MB) 
 Configuration file ( KAS) : 32kB
 Display : 320× 240 ( RGB) Pixel, 3.5-inch color STN display
 Temperature & humidity range : 23º C± 5º C, Relative humidity 85% or less ( no condensation) 
 Storage Temperature & humidity range : -20º C± 60º C, Relative humidity 85% or less( no condensation) 
 Operating Temperature & humidity range : 0º C± 40º C, Relative humidity 85% or less( no condensation) 
 PC Card type * 1 : Compact flash card ( Capacity: 32 / 64 / 128 / 256 / 512MB / 1GB) 
 Applicable standards : IEC 61010-1 CAT.III 600V Pollution degree 2
 IEC 61010-031, IEC 61326
 Power supply : AC 100V ~ 240V± 10% ( 45~ 65Hz) 
 Alkaline size AA battery LR6 ( 9V 1.5V × 6) or Ni-MH ( HR15-51) 
 Dimension : 175( L) × 120( W) × 68( D) mm
 Weight : approx. 900g ( including batteries) 
 Accessories : 7141( Voltage test lead) 
 7148 ( USB cable) 
 7170 ( Power cord) 
 9125 ( Carrying case) 
 8307 ( Compact flash card 128MB) 
 8319 ( CF Card reader) 
 Input terminal plate ( 6-kind) 
 Alkaline size AA battery ( LR6) × 6
 PQA MASTER ( PC Software) 
 Quick manual
 Cable marker × 32
 Optional accessories : 8124, 8125, 8126, 8127, 8128 ( Load current clamp sensor) 
 8129 ( Flexible clamp sensor) 
 8146, 8147, 8148 ( Leakage & Load current clamp sensor) * 2
 8141, 8142, 8143 ( Leakage clamp sensor) * 2
 7198 ( Small clips adaptor) 
 8322 ( Compact flash card 256MB) 
 8323 ( Compact flash card 1GB) 
 8312 ( Power supply adaptor) 
 8325F ( Flicker sensor) 
 9132 ( Carrying case ( for instrument) ) 
 
 * 1: Please refer to here for the CF cards which checked.
 * 2: Cannot be used for power measurement.
Informasi Dan Pemesanan Hub. Hary Nugroho  : 021.71601997 - 081806120636
Fax : 021.7318012  Email . alatsurveykita61@gmail.com
Tidak ada komentar: