KYORITSU Compact Power Meter 6305
-Comprehensive real-time monitoring, recording and analysis of single and 3-phase systems
-Voltage, Current, Power Factor and Frequency measurements
-Power analysis ( Active, Apparent and Reactive power)
-Energy analysis ( Active, Apparent and Reactive power)
-Active power accuracy:  ± 0.3% rdg ± 0.2% f.s.
-Automatic wiring check function to prevent incorrect connections
-Large memory capability ( 2GB) using built-in SD card interface
-Real time & remote measurements using Android application
-synchronous measurements between two units of KEW 6305
-Wide selection of clamp sensors allow measurements from 0.1A to 3000A
-The instrument automatically recognizes what kind of clamp sensor is connected to it
6305
CE
â € ¢ Windows software for data analysis and setting via USB port or Bluetooth
Free Android software " KEW smart 6305 " is available
on " Google Play Store " ( * )
Supporting Android ver. 2.2 - 4.0
WVGA ( 800 Ã — 480) resolution or higher
( * ) Please search " KEW Smart " in Google Play Store.
Communication charge may be incurred separately to download application.
NEW TRUE RMS USB Bluetooth  ®
Wiring connections 1P2W, 1P3W, 3P3W, 3P3W3A, 3P4W
Measurements Voltage, Current, Frequency, Active power
Parameters Apparent power, Reactive power, Active energy, Apparent energy,
Reactive energy, Power factor ( cos Î ¸ ) ,
Neutral current
Voltage :
Ranges [ RMS] 150.0 / 300.0 / 600.0V
Allowable input 10~ 110% of rating range
Display ranges 5~ 130% of each range
Accuracy  ± 0.2% rdg ± 0.2% f.s. ( sine wave, 45~ 65Hz)
Current :
Ranges [ RMS]
8128 ( 50A type ) : 1.000 / 5.000 / 10.00 / 25.00 / 50.00A / auto
8127 ( 100A type ) : 2.000 / 10.00 / 20.00 / 50.00 / 100.0A / auto
8126 ( 200A type ) : 4.000 / 20.00 / 40.00 / 100.0 / 200.0A / auto
8125 ( 500A type ) : 10.00 / 50.00 / 100.0 / 250.0 / 500.0A / auto
8124 ( 1000A type ) : 20.00 / 100.0 / 200.0 / 500.0 / 1000A / auto
8129 ( 3000A type ) : 300.0 / 1000 / 3000A
Allowable input 10~ 110% of each range
Display ranges 1~ 130% of each range
Accuracy  ± 0.2% rdg ± 0.2% f.s. + Accuracy of Clamp sensor ( sine wave, 45~ 65Hz)
( * ) + 1% f.s. at the lowest range
Crest factor Voltage: up to 2.5, Current: up to 3.0 ( with 90% fs or less)
Active power accuracy  ± 0.3% rdg ± 0.2% f.s. + Accuracy of Clamp sensor
( * ) + 1% f.s. when the lowest current ranges is selected.
Effect of power factor Active power: Â ± 1.0% rdg cos Î ¸ = Â ± 0.5 ( PF= 1)
Frequency meter range 40.0~ 70.0Hz
Frequency meter accuracy  ± 3dgt
Accuracy precondition PF= 1, Sine wave, 45~ 65Hz, 23Â º CÂ ± 5Â º C
Display update period 1 second
Operating temperature and humidity range 0~ + 50Â º C, less than 85% RH ( without condensation)
Storage temperature and humidity range -20~ + 60Â º C, less than 85% RH ( without condensation)
PC communication interface USB, Bluetooth
PC card interface SD card ( 2GB)
Applicable standards IEC 61010-1 CAT.III 600V
Power supply ( AC Line) AC100~ 240VÂ ± 10% ( 50/ 60Hz)
Power supply ( DC battery) LR6 or Ni-MH ( HR-15-51) Ã — 6 ( Battery charger not included) ,
Battery life approx. 15h ( LR6)
Power consumption 10VA ( max.)
Dimension 175( L) Ã — 120( W) Ã — 65( D) mm
Weight Approx. 800g ( including batteries)
Accessories 7141B ( Voltage test lead set: 4pcs)
7148 ( USB cable)
7170 ( Power cord)
9125 ( Carrying case)
8326-02 ( SD card 2GB)
KEW WINDOWS ( PC Software)
Battery ( LR6) Ã — 6
Quick manual
Calibration certificate
Optional 8124, 8125, 8126, 8127, 8128 ( Clamp sensor)
8129 ( Flexible clamp sensor)
8312 ( Power supply adaptor)
9132 ( Magnetic carrying case)
Set Model
KEW 6305-01
KEW 6305 Ã — 1
MODEL 8125 Ã — 3
7141B ( Voltage test lead set: 4pcs) Ã — 1
7148 ( USB cable) Ã — 1
7170 ( Power cord) Ã — 1
8326-02 ( SD card [ 2GB] ) Ã — 1
9125 ( Carrying case) Ã — 1
PC Software à — 1
Battery à — 6
Quick manual à — 1
Calibration certificate